Properties and Uses of the Product
This load break switch is designed for reliable operation in various distribution system applications, ensuring minimal energy losses and often exceeding standard efficiency ratings.
Key Features
- Vacuum Interrupters: The core technology involves vacuum interrupters that extinguish arcs without the need for oil or gas, which are common in traditional circuit breakers.
- Insulation Medium: The switch part uses VI (vacuum) for insulation, while the conduction part is insulated with Epoxy.
- Operation Mechanism: Features a magnetic actuator for precise and reliable switching operations.
- Control Circuit: Operates with AC230V or DC24V power.
Specifications
| PropertyValue |
| Rated Voltage | 15.5kV ~ 38kV |
| Rated Current | 630A |
| Frequency | 50Hz ~ 60Hz |
| Short-time Rated Current | 12.5kA |
| Rated Making Current (peak) | 32.5kA |
Detailed Specification Table
| Specification15.5 kV27.0 kV38.0 kV |
| Rated Current | 630 A | 630 A | 630 A |
| Rated Frequency | 50 Hz | 60 Hz | 50 Hz |
| Rated Short Time Current (RMS) | 12.5 kA | 12.5 kA | 12.5 kA |
| Rated Making Current (peak) | 32.5 kA | 32.5 kA | 32.5 kA |
| Power Frequency Withstand Voltage | 45 kV | 60 kV | 70 kV |
| Lightning Impulse Withstand Voltage | 110 kV | 150 kV | 170 kV |
Additional Technical Details
- Operation Mechanism: Magnetic actuator
- Mechanical endurance (times): Min. 10,000
- Insulation Medium: Switch Part: VI (vacuum), Conduction Part: Epoxy
- Applied Standard: IEC 62271-111
- Control Circuit Operation Power: AC230V, DC24V